Document No: LT0122 F3200 Installation & Programming Manual
Programming
Issue 2.7 5 July 2001 Page 6-35
Item Options Default
Anc 3 Relay Configuration, logic Supervision: disabled
equation, Text name Latching: No
Map to MAF: Yes
Isolatable: Yes
Testable: Yes
Sup ACT: Yes
No logic equation
RDU Protocol LCD/non-LCD LCD
RDU 1-8 Enabled/Disabled Disabled
Protocol A/B A
MCP Zone 1
TABLE 6.4.1
PROGRAMMABLE PARAMETERS (CONTINUED)
New Zealand mode Enable/Disable Enabled if NZ Display
present
Display extender board Installed/Not installed
Battery very low alarm Enable/Disable Disabled
Evac defect fault Enable/Disable Enabled in NZ mode
External defect fault Enable/Disable Enabled in NZ mode
TABLE 6.4.2
PROGRAMMABLE PARAMETERS (NEW ZEALAND ONLY)