Tyco F3200 Manual de usuario Pagina 112

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 284
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 111
F3200 Installation & Programming Manual Document No: LT0122
Programming System Configuration
Page 7-10 5 July 2001 Issue 2.7
VOLTAGE BANDS (CONTINUED)
Voltage bands and their interpretation for modes 1, 2 and 3 are shown in Table 7.2.1
following.
Band Voltage
Status Default Status
B5 21-22VFault (Open Circuit) Fault (Open Circuit)
B4 17.5-21V Normal Normal
B3 13-17.5V Programmable Normal (V1.XX software)
Instant alarm (V2.XX software)
B2 3-13V Alarm Alarm
(Detector Operated) (Detector Operated)
B1 0-3V Programmable Instant Alarm (Manual)
TABLE 7.2.1
AZC VOLTAGE BANDS FOR MODES 1-3
In Mode 4, for AZC normal the voltage is in B5 with pulses into B4 due to the active end-of-
line device. B2 is Alarm (valve operated). B3 is programmable to Alarm or Fault only
(default is Alarm). B1 is programmable (default is Fault). All other conditions are Fault
(Tamper).
Vista de pagina 111
1 2 ... 107 108 109 110 111 112 113 114 115 116 117 ... 283 284

Comentarios a estos manuales

Sin comentarios